APPLICATION
For control of temperature and humidity of room and/or discharge air in air-handling units comprising:
-
1 or 2 batteries for heating and/or
cooling.
-
1 modulating or On-Off humidification
battery.
-
1 air mixing unit or 1 heat regenerator.
Essential detectors:
Optional accessories:
-
1 flow temperature sensor.
-
1 pre-heating temperature sensor.
-
1 outside temperature
sensor.
-
1 room or air duct humidity sensor.
-
1 outside humidity sensor.
-
1 window dew-point sensor.
-
1 temperature set-point adjuster.
-
1 humidity set-point adjuster.
FEATURES
-
Power supply: 24V~.
-
Consumption: 5VA.
-
DIN 105 x 115 modular enclosure.
-
Protection: IP 40.
-
Digital programming by means of 4 keys and alphanumeric display.
-
Three 3-wire modulating outputs or On-Off in two stages (2 equal loads) or in three stages (2 unequal loads) configurable for:
-
control of room temperature in relation to heating and cooling values requested with, if required, summer outside compensation, minimum and maximum limits of flow in order to avoid cold air
currents, stratification of warm air and condensing in the air ducts.
-
control of flow temperature in relation to heating and cooling values requested with, if required, winter and summer
compensation.
-
control of pre-heating temperature at a value variable in relation to room temperature and
humidity.
-
control of room relative humidity in relation to humidification & dehumidification values requested.
-
One progressive 0 ... 10V- output configurable
for:
-
control of air mixture in relation to room-outside temperature (free cooling) or an enthalpic
comparison.
-
control of outside air for controlling room dehumidification with compensation for window dew
point.
-
control of heat regenerator in relation comparison room – outside temperatures.
-
Manual or automatic season switching of the controller functions and of the three-wire On-Off season control.
-
Variation of temperature & humidity set points by means of remote control.
-
Alarms for plant faults and for open or short sensor circuit.
Code |
|
Description |
Data sheet |
XTU 644 |
|
Temperature & humidity controller for 2-battery air-handling unit. |
E 135 |
ACB
460 |
|
Plug-in per comunicazione via
. |
- |
DETECTORS & ACCESSORIES
Code |
|
Description |
Application
range |
Sensing elem. or signal |
Data sheet |
STA
010 |
|
Air duct temperature sensor (extract, discharge, condensation). |
0 ...
60
°C |
NTC 10
kΩ |
N
150 |
SAB
010 |
|
Room temperature
sensor in wall mounting case 80 x 80 x 32. |
0 ...
40
°C |
NTC 10
kΩ |
N
111 |
STA
001 |
|
Air duct temperature sensor (external). |
-40 ...
40
°C |
NTC 1
kΩ |
N
150 |
SAE
001 |
|
Outside temperature sensor. |
-40
... 40
°C |
NTC 1
kΩ |
N
120 |
STV
010 |
|
Windows temperature sensor
(dew point). |
0 ...
40
°C |
NTC 10
kΩ |
N
160 |
SUR
704 |
|
Air duct relative humidity
sensor. |
10 ...
90
% |
0 ...
10
V |
N
221 |
SUT
714 |
|
Air duct relative humidity sensor (for swimming pool). |
10 ...
90 % |
0 ...
10
V- |
N
222 |
SAU
914 |
|
Relative humidity |
10 ...
90
% |
0 ...
10
V |
N
227 |
& temperature
sensor. |
0 ...
40
°C |
NTC 10
kΩ |
CDB
100 |
|
Temperature setpoint adjuster. |
5 ...
5
°C |
- |
- |
CDB
200 |
|
Humidity setpoint adjuster. |
10
... 10
% |
- |
- |
|