TEMPERATURE & HUMIDITY CONTROLLER FOR ONE-BATTERY AIR-HANDLING UNITS
OPTIONAL TELEMANAGEMENT

XTU 614

 Path - First page - Products - Controllers for temperature & Humudity - XTU 614

  • TELEMANAGEMENT : Enabled with ACB 460 accessory.

APPLICATION

For control of room temperature and humidity and/or discharge air in air-handling units comprising:

  • 1 battery for heating and/or cooling or pre-heating.

  • 1 On-Off humidification battery.

  • 1 air mixing unit or 1 heat regenerator.

Essential detectors:

  • 1 room or air duct temperature detector.

Optional accessories:

  • 1 flow or pre-heating temperature detector.

  • 1 outside temperature detector.

  • 1 room or air duct hunidity detector.

  • 1 window dew-point detector.

  • 1 battery Frosprot detector.

  • 1 temperature set-point adjuster

  • 1 humidity set-point adjuster.

FEATURES

  • Power supply: 24V~

  • Consumption: 5VA

  • DIN 105 x 115 modular enclosure

  • Protection: IP 40.

  • Digital programming by means of 4 keys and alphanumeric display.

  • Timed programming: 24hour and 7day.

  • Programming with dates: 25 holiday periods; winter season; summer season.

  • Automatic switching GMT – BST..

  • One 3-wire modulating output or On-Off in 2 stages (2 equal loads) or in 3 stages (2 unequal loads) configurable for:

    • control of winter & summer room temperature with, if required, summer outside compensation, minimum & maximum limits of flow in order to avoid cold air currents, stratification of hot air and condensing in the air ducts.

    • control of flow temperature at fixed point with, if required, winter & summer compensation.

    • control of pre-heating temperature at a variable value in relation to room temperature & humidity.

  • 1 On-Off output for control humidifying unit for control of relative humidity at fixed point.

  • 1 progressive 0 ... 10 V- output configurable for:

    • control of mixture outside air in relation to comparison room - outside temperatures.

    • control outside air for control of room dehumidification with compensation for windows dew point.

    • control of heat regenerator in relation to comparison room – outside temperatures.

  • Two On-Off outputs for control of fan and pump according to timed program in use.

  • Control Frosprot temperature battery.

  • Manual or automatic season switching of controller functions and of On-Off 3-wire season switch.

  • Variation of temperature & humidity set points by means of remote control.

  • Alarms for plant faults and for open or short sensor circuit.

Code  

Description

Data sheet

XTU 614  

Temperature & humidity controller for 1 battery air-handling unit.

E 134

DETECTORS & ACCESSORIES

Code   Description Application range

Sensing elem. or signal

Data sheet
ACB 460   Plug-in for communicating via . - - T 433
STA 010   Air duct temperature sensor (extract, discharge, condensation). 0 ... 60 °C NTC 10 kΩ N 150
SAB 010   Room temperature sensor in wall mounting case 80 x 80 x 32. 0 ... 40 °C NTC 10 kΩ N 111
STA 001   Air duct temperature sensor (external). -40 ... 40 °C NTC 1 kΩ N 150
SAE 001   Outside temperature sensor. -40 ... 40 °C NTC 1 kΩ N 120
SAF 010   Cable-type temperature sensor (Frosprot). 0 ... 40 °C NTC 10 kΩ N 145
STV 010   Windows temperature sensor (dew point) 0 ... 40 °C NTC 10 kΩ N 160
SUR 704   Air duct relative humidity sensor. 10 ... 90 % 0 ... 10 V­ N 221
SUT 714   Air duct relative humidity sensor (for swimming pool). 10 ... 90 % 0 ... 10 V­ N 222
SAU 914   Relative humidity 10 ... 90 % 0 ... 10 V­ N 227
& temperature sensor. 0 ... 40 °C NTC 10 kΩ
CDB 100   Temperature setpoint adjuster. ­5 ... 5 °C - -
CDB 200   Remote control for changing program in use. ­10 ... 10 % - -