OPTIMISING COMPENSATOR OF TEMPERATURE & FLOW
OPTIONAL TELEMANAGEMENT

XTP 600

clicca sull'immagine per ingrandire

 Path - First page - ProductsOptimising Compensator - XTE 600

  • TELEMANAGEMENT : Enabled with ACB 468 accessory.

APPLICATION

Designed for the compensated control of one central heating site and for the On-Off control of a water heater for the production of DHW.
Optimises the performance of condensation boilers.
Data exchange with other controllers by means of serial connection.
Essential sensors: 1 external sensor, 1 heating flow sensor.
Optional accessories: 1 room sensor, 1 water heater sensor, 1 flue gases sensor, 1 remote control, 1 return site sensor.

FEATURES

  • Power supply: 230 V~; Consumption: 5 VA; DIN 105 x 115 modular enclosure; Protection: IP 40. 

  • Digital programming by means of 4 operating keys and alphanumeric display.

  • Setting dates of heating season and automatic switching GMT – BST.

  • Seven 24hour programs, two 7day programs, 25 holiday periods and one Special period with dates.

  • Compensated control of heating site:
    – Modulating control valve with 3-wire reversible actuator.
    – Modulating control of variable-speed pump (compensated control of the flow)
    – On-Off control of heating pump in relation to times and thermal demand..
    – Optimisation of start and stop times.
    – Minimum and maximum limits of flow temperature.
    – Manual adjustment of origin of heating curve (compensation for intermediate seasons)..
    – Automatic adjustment of heating curve in relation to room temperature (Ambient Authority).
    – “Eco Off” function: closure of site when outside temperature mild.
    – Summer Site Exercise of valve and pump.

  • Control water heater for production DHW:
    – On-Off control water heater pump by timed programs independent of heating.
    – “Priority water heater” function (closure heating valve).
    – Antibacteria function: once a week 70°C for 90 minutes.

  • Three On-Off alarm inputs.

  • 1 configurable input: remote control or flue gases temperature Pt 1 kΩ and On-Off alarm.

  • Alarms for operation site and for short- or open- sensor circuits.

  • Metering degree-days.

Code  

Description

Data sheet

XTP 600  

Optimising compensator.

B 243

DETECTORS AND ACCESSORIES

Code   Description Application range

Sensing element

Data sheet
ACB 468   Plug-in for communication via . - - T 433
SAE 001   Outside temperature sensor. -40 ... 40 °C NTC 1 kΩ N 120
SIH 010   Immersion temperature sensor. 0 ... 99 °C NTC 10 kΩ N 140
SCH 010   Surface temperature sensor. 0 ... 99 °C NTC 10 kΩ N 130
SAB 010   Room temperature sensor in wall mounting case 80 x 80 x 32. 0 ... 40 °C NTC 10 kΩ N 111
SAI 010   Irradiated sensor in 80 x 80 x 26 housing for wall mounting 0 ... 40 °C NTC 10 kΩ N 111
STF 001   Flue gases temperature sensor. 0 ... 500 °C Pt 1 kΩ N 165
CDB 300   Remote control to modify program in use.  - - N 710