Power supply: 230V~.
-
Consumption: 5VA.
-
DIN 105 x 115 modular enclosure.
-
Protection: IP 40.
-
Digital programming by means of 4 keys and alphanumeric display.
-
Setting dates for heating season and automatic switching between GMT –
BST.
-
Seven 24hour programs, two 7day programs, 25 holiday periods and one special period with dates.
-
Fixed point or variable control of boiler according to max. temperature requested by heating, etc zones:
-
On-Off control of one single- or two-stage burner or 2 single-stage
burners.
-
Control boiler anticondensing (closure of heating valve).
-
Theoretical metering of operating hours of the two burner stages.
-
Compensated control of centralised heating plant room:
-
Modulating control of valve by 3-wire reversible
actuator.
-
Control of heating pump in relation to times and demand for
heat.
-
Optimisation of start and stop
times.
-
Minimum and maximum limits of flow temperature.
-
Manual correction heating curve point of origin (compensation for intermediate
seasons).
-
Automatic adjustment of heating curve in relation to room temperature
(ambient authority).
-
Eco Off function: switching off heating zones when weather
mild.
-
Remote control for changing program in use (as alternative to temperature flue gases & On-Off alarm).
-
Control production of DHW:
-
On-Off control of calorifier pump by timed programs independent of
heating.
-
"DHW priority" (closure heating valve).
-
Antibacteria function: once a week at 70
°C for 90 minutes.
-
Summer exercise function for valves and
pumps.
-
Three inputs On-Off alarms.
-
One configurable input: remote control or flue gases temperature Pt 1kΩ and On-Off
alarm.
-
One configurable input: measurement 4
... 20mA or flue gases temperature Pt 1 kΩ and On-Off alarm.
-
Alarms for plant malfunctioning and for open or short sensor
circuit.
-
Degree-days metering.