Power supply: 230V~.
-
Consumption: 5VA.
-
DIN 105 x 115 modular enclosure.
-
Protection: IP 40.
-
Digital programming by means of 4 keys and alphanumeric display.
-
Entering dates of heating season and automatic switching BST -
GMT.
-
Seven 24hour programs, two 7day programs, 25 holiday periods and one special period with dates.
-
Compensated control of heating plant room:
-
Modulating control of valve with 3-wire reversible actuator or On-Off burner in two
stages.
-
Control heating pump according to times and demand for
heat.
-
Optimisation switching on and off
times.
-
Minimum and maximum limits flow temperature.
-
Manual correction heating curve origin
(compensation intermediate seasons).
-
Automatic correction of heating curve in relation to room temperature
(ambient authority).
-
Eco Off function: shutdown of plant when weather
mild.
-
Control boiler anticondensing temperature
(closure heating valve).
-
Summer plant exercise valve and
pump.
-
Remote control for changing timed program in use
(as alternative to input flue gases temperature and On-Off alarm).
-
Control DHW production:
-
On-Off control DHW loading pump with timed programs independent of
heating.
-
"Priority DHW" function (closure heating valve).
-
"Antibacteria" function: once a week 70° for 90
minutes.
-
Three On-Off alarm inputs.
-
One 4 ... 20 mA measurement input.
-
One configurable input: remote control or temperature flue gases Pt 1 kΩ and On-Off
alarm.
-
Alarms for plant faults and for open or short sensor circuit.
-
Degree-days metering.