- TELEMANAGEMENT
: Enabled using ACB 400 accessory.
APPLICATION
Designed for sequencing two boilers with one- or two-stage burners and shut-off valves. Control of primary manifold temperature with temperature measurement by means of a sensor on manifold or two sensors on the boilers..
Essential detectors:
Optional accessories:
FEATURES
-
Power supply: 230V~;
-
Consumption: 5VA;
-
DIN 105 X 115 modular enclosure;
-
Protection: IP 40.
-
Digital programming by means of four keys and alphanumeric display.
-
Setting dates of heating season and automatic switching GMT – BST.Seven 24hour periods and two 7day
programs.
-
25 holiday programs and one special period with
dates.
-
Control of zone temperature:
- Sequencing: manual switching from display or timed
automatic.
- Automatic inversion of sequence in event of lockout of lead boiler.
- Enabling of lag boiler according to mean temperature of zone.
- Digital control of burners and of valves with adjustable delay
closure.
- Theoretical metering of burner operating hours.
- Two inputs for measurement and alarms for flue gas temperature and for lockout
burners.
- Three digital alarm inputs.
- Alarms for plant faults and for open or short sensor
circuit.
| Code |
|
Description |
Data sheet |
| XTC 638 |
|
Temperature controller for a modulating boiler, for several boiler in sequence and other functions
|
A 610 |
DETECTORS AND ACCESSORIES
| Code |
|
Description |
Application
range |
Sensing element |
Data sheet |
| ACB 460 |
|
Plug-in for communicating via . |
- |
- |
T
433 |
| SAE 001 |
|
Outside temperature
sensor. |
-40 ...
40 °C |
NTC 1 kΩ |
N
120 |
| SIH 010 |
|
Immersion temperature
sensor. |
0 ...
99 °C |
NTC 10 kΩ |
N
140 |
| SCH
010 |
|
Surface temperature sensor |
|
NTC 10 kΩ |
N
130 |
| SAB 010 |
|
Room temperature sensor |
0 ...
40 °C |
NTC 10 kΩ |
N
111 |
| STF 001 |
|
Flue gases temperature
sensor. |
0 ... 500 °C |
Pt 1 kΩ |
N
165 |
|