first page

MODULATING ELECTRONIC CONTROLLERS FOR UNDERFLOOR PANELS

RTP 82

NOW OBSOLETE

click on picture to enlarge
 Path - First page - ProductsThermostats and ambient controllers - RTP 82

APPLICATION

Room temperature regulation for single-family or zoned heating installations by PI modulating control action of a valve operated by a reversible actuator.

The room temperature is monitored by an NTC 10 kΩ sensing element inside the controller.

Controls flow temperature in relation to shift in room temperature with a maximum limit of 45 °C.

Essential detectors for all models:

  • 1 plant flow detector.

Essential detectors for /D models:

  • 1 room detector.

FEATURES

  • Power supply: 230 V ~.

  • Consumption: 4 VA.

  • Protection: IP 20.

  • Voltage-free output contacts: rating 250 V ~, 5 (3) A.

  • Control of actuators with run times: 60 ... 120 seconds.

  • Setting range: 5...30 °C.

  • PI control action.

  • Proportional band: ± 1 °C.

  • Possibility of limiting setting range by means of pins supplied on request.

 

Code  

Description 

Data sheet

RTP 825   Controller with 24-hour timeswitch and incorporating room detector. B 335
RTP 825/D   Controller with 24-hour timeswitch for remote room detector.
RTP 826   Controller with 7-day timeswitch and incorporating room detector.
RTP 826/D   Controller with 7-day timeswitch for remote room detector.

DETECTORS & ACCESSORIES

Code   Description Setting range

Sensing element

Data sheet

for all models:

SIH 010   Plant flow immersion temperature detector. 0 ... 99 °C NTC 10 kΩ N 140

for /D models:

SAB 010   Room temperature detector. 0 ... 40 °C NTC 10 kΩ N 111
SAB 020  

Room detector for large spaces (2 in parallel).

0 ... 40 °C NTC 20 kΩ N 111