first page

GAS DETECTOR 144 x 144 WITH PRE-ALARM FOR PANEL MOUNTING

RFG 782

click on picture to enlarge

 Path - First page - Products - Gas Detectors - RFG 782

APPLICATION

Monitors, by means of one or two remote sensors, the concentration of gas in the air. When this concentration exceeds the 1st threshold, the detector activates the pre-alarm relay and when the concentration exceeds the 2nd threshold it activates the operational relay and the external alarms.

Complies with CEI EN 50194 and CEI EN 50244 (methano e LPG); CEI EN 50291 and CEI EN 50292 (CO) regulations.

Essential sensors : 

  • 1 or 2 sensors for methane, LPG, carbon monoxide.

FEATURES

  • Power supply: 230 V ~ o 12 V–.

  • Consumption: 6 VA.

  • Enclosure: DIN 144 x 144.

  • Protection IP 40.

  • Adjustable pre-alarm and alarm thresholds: methane:

    • Methane = 0.25...0,8%.

    • LPG = 0.06...0.35%.

    • CO = 0.005...0.05%;

  • Signals pre-alarm, alarm and fault in sensors.

  • Voltage-free SPDT outputs: rating: 250 V~, 10 (2.5) A for control of N.O. or N.C. valves.

Code   Description Data sheet
RFG 782   Gas leak detector with pre-alarm for 1 or 2 remote sensors. G 610

GAS SENSOR

          Connection length  
Code   Gas Enclosure Protection 3 x 1mm2 3 x 1.5mm2

Data sheet

SGC 300/M   Methane Domestic (90 x 65 x 42 mm) IP 30 50 m 75 m -
SGC 300/P   LPG Domestic (90 x 65 x 42 mm) IP 30 50 m 75 m -
SGC 301   CO Domestic (90 x 65 x 42 mm) IP 30 50 m 75 m -
SGR 300/M   Methane Commercial (80 x 80 x 42 mm) IP 44 50 m 75 m -
SGR 300/P   GPL Commercial (80 x 80 x 42 mm) IP 44 50 m 75 m -
SGR 301   CO Commercial (80 x 80 x 42 mm) IP 44 50 m 75 m -