APPLICATION
Compact
unit for control of temperature at fixed point in DHW distribution circuits.
The
Antilegionnaire function comes into operation once a week (adjustable day and
time). Increases
the temperature of the distribution circuit (valve completely open) for a period
of time proportional to the temperature itself: high temperature (> 65°C) = short period (30 min.); low temperature (<55°C)
= long period (7 hours). Comprises:
FEATURES
-
Power supply: 230 V ~.
-
Protection: IP 54.
-
Consumption:
MAS 6.. = 6 VA; MAS 7.. = 9 VA.
-
Working
pressure and maximum differential: 6 bar.
-
Proportional band: ± 5 ... ± 20
°C.
Code |
|
DN |
Flow
l/min.
(1) |
Kvs
(2) m3/h |
Setting
range |
Data
sheet |
inches |
mm. |
MAS
615/AL |
|
1/2" |
15 |
40 |
2.5 |
30 ...
70 °C |
C
512 |
MAS
620/AL |
|
3/4" |
20 |
70 |
5 |
30 ...
70 °C |
MAS
625/AL |
|
1" |
25 |
130 |
9 |
30 ...
70 °C |
MAS
632/AL |
|
1"
1/4 |
32 |
180 |
13.5 |
30 ...
70 °C |
|
|
|
|
|
|
|
MAS 740/AL |
|
1"1/2 |
40 |
270 |
19.2 |
30 ...
70 °C |
MAS 750/AL |
|
2" |
50 |
390 |
28.6 |
30 ...
70 °C |
PRESSURE DROP
|
|
|