APPLICATION
Without power they are closed, when
powered they are open. Approved Class A Group 2: GASTEC PIN: 63AQ1350, October
1995.
FEATURES
-
Constructed to EN standard.
-
Protection IP 54.
-
Brass body.
-
Working temperature: -15 ... + 60 °C.
-
Mounted with coil axis within 90° of
vertical.
|
|
|
Power
supply
|
|
Flow
rate m3/h (2)
|
|
Code |
|
DN
|
V
|
W
|
P.max (1)
mbar
|
0.5
mbar
|
1 mbar
|
Data sheet |
GNC
815/OT
|
|
1/2"
|
230 V
~
|
22
|
200
|
0.7
|
1
|
G 912
|
-
(1) Maximum working
pressure
-
(2) Flow of methane with
pressure drop of 0.5 mbar (5mmWG) and 1 mbar (10 mmWG).
-
100 mbar = 10 kPa = 1,000 mm.WG.
PRESSURE DROP GNC

FEATURES OF GAS SOLENOID VALVES
Model |
Operation |
Advantages |
Disadvantages |
Normally
closed GNC
|
-
Without power closes.
-
With power
opens.
|
-
Ideal for boiler plants.
-
In event gas leak, detector switches off
power to valve.
-
Power returns only with manual
re-set of detector.
-
In event mains supply failure valve
closes; when power returns valve re-opens automatically.
|
-
Not recommended for kitchens without
thermo-couple.
-
In event failure of mains power, valve closes and flame
goes out; when power returns valve re-opens and gas escapes causing a dangerous
situation.
|
|