OPTIMISING COMPENSATOR
FOR HEATING PLANT ROOM
OPTIONAL TELEMANAGEMENT 

DTE 611

NOW OBSOLETE

 Path - First page - ProductsOptimising Compensator - DTE 611

 

APPLICATION

Designed for control of small and medium-size heating plant rooms comprising:

  • 1 single- or two-stage boiler, or double furnace (two single-stage burners).

  • 1 centralised heating plant room.

  • 1 calorifier for DHW.

  • Telemanagement enabled via   : to allow communications to a local or remote PC via a modem .

  • Communications with other controllers via serial connection to share sensor information.

Essential detectors:

  • 1 outside sensor.

  • 1 heating flow sensor.

  • 1 boiler sensor.

Optional accessories:

  • 1 room sensor.

  • 1 DHW sensor.

  • 1 or 2 flue gas sensors.

  • 1 remote override.

FEATURES

  • Power supply: 230V~.

  • Consumption: 5VA.

  • DIN 105 x 115 modular enclosure.

  • Protection: IP 40.

  • Digital programming by means of 4 keys and alphanumeric display.

  • Setting dates for heating season and automatic switching between GMT – BST.

  • Seven 24hour programs, two 7day programs, 25 holiday periods and one special period with dates.

  • Fixed point or variable control of boiler according to max. temperature requested by heating, etc zones:

    • On-Off control of one single- or two-stage burner or 2 single-stage burners.

    • Control boiler anticondensing (closure of heating valve).

    • Theoretical metering of operating hours of the two burner stages.

  • Compensated control of centralised heating plant room:

    • Modulating control of valve by 3-wire reversible actuator.

    • Control of heating pump in relation to times and demand for heat.

    • Optimisation of start and stop times.

    • Minimum and maximum limits of flow temperature.

    • Manual correction heating curve point of origin (compensation for intermediate seasons).

    • Automatic adjustment of heating curve in relation to room temperature (ambient authority).

    • Eco Off function: switching off heating zones when weather mild.

    • Remote override for changing program in use (as alternative to temperature flue gases & On-Off alarm).

  • Control production of DHW:

    • On-Off control of calorifier pump by timed programs independent of heating.

    • "DHW priority" (closure heating valve).

    • Antibacteria function: once a week at 70 °C for 90 minutes.

  • Summer exercise function for valves and pumps.

  • Three inputs On-Off alarms.

  • One configurable input: remote control or flue gases temperature Pt 1kΩ and On-Off alarm.

  • One configurable input: measurement 4 ... 20mA or flue gases temperature Pt 1 kΩ and On-Off alarm.

  • Alarms for plant malfunctioning and for open or short sensor circuit.

  • Degree-days metering.

Code  

Description

Data sheet

DTE 611  

Optimising compensator with N.C. relay for control boiler.

B 251

DETECTORS AND ACCESSORIES

Code   Description Application range

Sensing element

Data sheet
SAE 001   Outside temperature sensor. -40 ... 40 °C NTC 1 kΩ N 120
SIH 010   Immersion temperature sensor. 0 ... 99 °C NTC 10 kΩ N 140
SCH 010   Surface temperature sensor. 0 ... 99 °C NTC 10 kΩ N 130
SAB 010   Room temperature sensor in wall mounting case 80 x 80 x 32. 0 ... 40 °C NTC 10 kΩ N 111
STF 001   Flue gases temperature sensor. 0 ... 500 °C Pt 1 kΩ N 165
CDB 300   Remote control to modify program in use. - - -