APPLICATION

In combination with 1,2 or 3 relay control modules ISC 648, DTC 648 can sequence two or more one- or two-stage boilers, with or without shut-off valves, for the control of the primary manifold or flow temperature in a heating plant, and control the temperature of a DHW plant.

  • compatible.

  • compatible.

Essential accessories:

  • 1 detector on manifold or heating flow.

Optional accessories:

  • 1 outside detector.

  • 1 boiler detector.

FEATURES

  • Power supply: 230 V ~.

  • Consumption: 5 VA.

  • DIN 105 x 115 modular enclosure.

  • Protection: IP 40.

  • Digital programming by means of four operating keys and alphanumeric display.

  • Setting dates for heating season and automatic switching GMT- BST.

  • Seven 24-hour programmes, two 7-day programmes, 25 holiday periods and one special period with date setting.

  • Control temperature primary manifold or heating plant flow:

    • Fixed point.

    • Variable in relation to outside temperature.

    • Variable in relation to.temperature requested by heating zones with min. and max. flow temperature.

  • Timed On-Off control of primary manifold or heating plant pump.

  • Minimum and maximum limits flow temperature.

  • Manual correction heating curve origin to compensate for seasonal weather changes.

  • Eco Off  function.

  • Summer plant exercise.

  • Sequence: Manual inversion from display or timed automatic:

    • Control calorifier for production DHW: - On-Off control calorifier pump with timed events programmes independent of heating.

    • Antibacteria function: once a week at 70 °C for 90 minutes.

  • One On-Off alarm input, one measurement input 4 ... 20 mA and one input flue gases temperature Pt 1 kΩ.

  • Alarms for controller fault and for short or open detector circuits.

Code  

Description 

Data sheet

DTC 648  

Compensator for boiler sequencing.

A 410

POSSIBLE COMBINATIONS

Controllers Boilers with isolation valves 1-stage burners Boilers without isolation valves 1-stage burners Boilers with isolation valves 2-stage burners Boilers without isolation valves 2-stage burners
1 DTC 648 + 1 ISC 648 up to 4 up to a 8 up to 4 up to 4
1 DTC 648 + 2 ISC 648 up to a 8 up to 16 up to 8 up to 8
1 DTC 648 + 3 ISC 648 up to a 12 up to 24 up to 12 up to 12

DETECTORS & ACCESSORIES

Code   Description Range

Sensing element

Data sheet
ISC 648  

Relay module - Essential.

A 450
SAE 001   Outside temperature detector. -30 ... 40 °C NTC 1 kΩ N 120
SIH 010   Sonda di temperatura ad immersione con pozzetto ottone. 0 ... 99 °C NTC 10 kΩ N 140
STH 001   Sonda alta temperatura ad immersione con pozzetto inox. 0 ... 300 °C Pt 1 kΩ N 140