OPTIMISING COMPENSATOR "SLAVE"
OPTIONAL TELEMANAGEMENT 

DSE 600

NOW OBSOLETE

 Path - First page - ProductsOptimising Compensator - DSE 600

APPLICATION

Suitable for compensated control of one centralised heating plant room and for the On-Off control of a DHW calorifier.

  • Operates only if connected via to a "PRIMARY" controller.

Essential detectors:

  • 1 outside sensor.

  • 1 flow sensor.

Optional accessories:

  • 1 room sensor.

  • 1 measurement 4 ... 20 mA sensor.

  • 1 remote control.

FEATURES

  • Power supply: 230V~.

  • Consumption: 5VA.

  • DIN 105 x 115 modular enclosure.

  • Protection: IP 40.

  • Digital programming by means of 4 keys and alphanumeric display.

  • Entering dates of heating season and automatic switching BST - GMT.

  • Seven 24hour programs, two 7day programs, 25 holiday periods and one special period with dates. 

  • Compensated control of heating plant room:

  • Modulating control of valve with 3-wire reversible actuator or On-Off burner in two stages.

    • Control heating pump according to times and demand for heat.

    • Optimisation switching on and off times.

    • Minimum and maximum limits flow temperature.

    • Manual correction heating curve origin (compensation intermediate seasons).

    • Automatic correction of heating curve in relation to room temperature (ambient authority).

    • Eco Off function: shutdown of plant when weather mild.

    • Control boiler anticondensing temperature (closure heating valve).

    • Summer plant exercise valve and pump.

    • Remote control for changing timed program in use (as alternative to input flue gases temperature and On-Off alarm).

  • Control DHW production:

    • On-Off control DHW loading pump with timed programs independent of heating.

    • "Priority DHW" function (closure heating valve).

    • "Antibacteria" function: once a week 70° for 90 minutes.

  • Three On-Off alarm inputs.

  • One 4 ... 20 mA measurement input.

  • One configurable input: remote control or temperature flue gases Pt 1 kΩ and On-Off alarm.

  • Alarms for plant faults and for open or short sensor circuit.

  • Degree-days metering.

Code  

Description

Data sheet

DSE 600  

Optimising compensator.

B 265

DETECTORS AND ACCESSORIES

Code   Description Application range

Sensing element

Data sheet
SAE 001   Outside temperature sensor. -40 ... 40 °C NTC 1 kΩ N 120
SIH 010   Immersion temperature sensor. 0 ... 99 °C NTC 10 kΩ N 140
SCH 010   Surface temperature sensor. 0 ... 99 °C NTC 10 kΩ N 130
SAB 010   Room temperature sensor in wall mounting case 80 x 80 x 32. 0 ... 40 °C NTC 10 kΩ N 111
STF 001   Flue gases temperature sensor. 0 ... 500 °C Pt 1 kΩ N 165
CDB 300   Remote control to modify program in use.  - - -