UNIVERSAL CONTROLLER

DRU 614-618

click on picture to enlarge

 Path - First page - ProductsControllers for Various Uses - DRU 614-618

APPLICATION

  • DRU 614 controller can be used to control:

    • temperature measured by a passive detector:

      • NTC 1kΩ (–30 ... +40 °C);

      • NTC 10 kΩ (0 ... 99 °C);

      • PT 1 kΩ (0 ... 300 °C).

    • or a physical quantity (pressure, level and so on) measured by an active detector:

      • 0 ... 10 V–;

      • 4 ... 20 mA.

    • with control of:

      • three-point modulating valve;

      • or On-Off electric actuator with 1,2,3,4 steps;

      • or converter of a three-point modulating signal into progressive signal 0 ... 10 V–.

  • compatible.

Essential accessories:

  • 1 thermistor type or voltage/current type.

Optional accessories:

  • 1 set point adjuster.

FEATURES

  • Power supply: 24 V ~ (DRU 614); 230 V ~ (DRU 618).

  • Consumption: 5 VA.

  • DIN 105 x 115 modular case.

  • Protection: IP 40.

  • Digital programming by means of four operating keys and alphanumeric display.

  • Control at fixed point:

    • Three-wire modulating control or On-Off control in sequence of 2, 3 or 4 stages.

    • Two On-Off controls in relation to two adjustable thresholds of output signal or of measurement range.

    • Adjustment of set point by means of remote control.

  • One On-Off alarm input.

  • Two configurable inputs:

    • remote control for inversion of control action or On-Off alarms.

  • Alarms for operational controller fault for short or open detector circuits.

Code  

Description 

Data sheet

DRU 614  

 Universal controller. Power supply 24 V ~

D 410

DRU 618  

 Universal controller. Power supply 230 V ~

D 410

DETECTORS & ACCESSORIES

Code   Description Setting range

Sensing element

Data sheet
SIH 010   Immersion temperature detector. 0 ... 99 °C NTC 10 kΩ N 140
STH 001   Immersion water temp. detector. 0 ... 300 °C PT 1 kΩ
SAF 001   Cable-type temperature detector. -30 ... 40 °C NTC 1 kΩ N 145
SAB 010   Room temperature detector. 0 ... 40 °C NTC 10 kΩ N 111
SUR 704   Relative humidity detector. 10 ... 90 % 0 ... 10 V– N 221
SUT 714   Relative humidity and temperature detector. 10 ... 90% 0 ... 10 V– N 222
SAU 914   Relative humidity 10 ... 90 % 0 ... 10 V­ N 227
& temperature sensor. 0 ... 40 °C NTC 10 kΩ
SPW 101   Absolute pressure detector for liquids or steam. 0 ... 1 bar 0 ... 10 V– N 410
SPW 102   Absolute pressure detector for liquids or steam. 0 ... 2,5 bar 0 ... 10 V–
SPW 106   Absolute pressure detector for liquids or steam. 0 ... 5 bar 0 ... 10 V–
SPW 116   Absolute pressure detector for liquids or steam. 0 ... 16 bar 0 ... 10 V–
SDW 101   Differential pressure detector for liquids or steam. 0 ... 1 bar 0 ... 10 V– N 420
SDW 102   Differential pressure detector for liquids or steam. 0 ... 2,5 bar 0 ... 10 V–
SDW 106   Differential pressure detector for liquids or steam. 0 ... 6 bar 0 ... 10 V–
SDA 701   Differential pressure detector for air. 0 ... 1 mbar 0 ... 10 V– N 430
SDA 703   Differential pressure detector for air. 0 ... 3 mbar 0 ... 10 V–
SDA 705   Differential pressure detector for air. 0 ... 5 mbar 0 ... 10 V–
SDA 730   Differential pressure detector for air. 0 ... 30 mbar 0 ... 10 V–
CDB 100   Setpoint adjuster.