COMPENSATING CONTROLLER WITH SEASON SWITCHING
OPTIONAL TELEMANAGEMENT

DCS 633

NOW OBSOLETE

 Path - First page - ProductsCompensator - DCS 633

APPLICATION

Designed for winter and summer compensated control in water flow in centralised plants with fan coils or under floor heating

Essential detectors:

  • 1 outside sensor.

  • 1 flow sensor.

Optional accessories:

  • 1 room temperature or temperature & humidity sensor.

  • 1 remote control.

FEATURES

  • Power supply: 230V~.

  • Consumption: 5VA.

  • DIN 105 x 115 modular enclosure.

  • Protection: IP 40.

  • Digital programming by means of four keys and alphanumeric display.

  • Seven 24hour programs, two 7day programs, 25 holiday periods & one special period with dates.

  • Manual or automatic season switching with dates or by external switch (as alternative to two digital alarm inputs).

  • Automatic switching BST - GMT.

  • Compensated or fixed point control summer and winter flow temperature:

    • Modulating control of valve by 3-wire reversible actuator or On-Off control in two stages.

    • Control of heating pump in relation to times and demand for heat.

    • Minimum & maximum limits for flow temperature.

    • Manual correction of heating curve point of origin (compensation intermediate seasons).

    • Automatic correction of heating curve in relation to room temperature (Ambient Authority).

    • Control of ambient dew-point for summer cooling plants with under floor panels.

    • Control boiler anticondensing temperature (closure heating valve).

    • Remote control for adjusting program in use.

  • Relay output for centralized season switching.

  • Two On-Off alarm inputs (as alternative to external switch for season switching).

  • Alarms for plant faults and for open or short sensor circuit.

Code  

Description 

Sata sheet

DCS 633  

Compensating controller with season switching.

B 270

DETECTORS AND ACCESSORIES

Code   Description Application range

Sensing element

Data sheet
SAE 001   Outside temperature sensor. -40 ... 40 °C NTC 1 kΩ N 120
SIH 010   Immersion temperature sensor. 0 ... 99 °C NTC 10 kΩ N 140
SAB 010   Room temperature sensor in wall mounting case 80 x 80 x 32. 0 ... 40 °C NTC 10 kΩ N 111
SAU 914   Relative humidity 10 ... 90 % 0 ... 10 V– N 227
& temperature sensor. 0 ... 40 °C NTC 10 kΩ
CDB 333   Remote control for adjusting program in use. - - -