DAMPER ACTUATORS

CSL ... - CSN ... - CSS ... - CSG ...

 Path - First page - Products - Damper Actuators - CS.

APPLICATION

Actuators suitable for operating dampers in air handling sites.
Rotary movement with 90° rotation angle.
Mounted directly on damper rod.

FEATURES

  • Power supply: 230 V~ or 24 V~/-.

  • Protection: IP 54.

Code   Power supply V ~ (VA) Control Auxiliary contacts Dampers m2 Torque N/m Run sec. Data sheet
CSL 138   230 V ~ (4) 2 o 3 points No 1 5 150 E 921
CSL 138/C   230 V ~ (4) 2 o 3 points 1 1 5 150
CSL 134   24 V ~/ (2) 2 o 3 points No 1 5 150
CSL 134/C   24 V ~/ (2) 2 o 3 points 1 1 5 150
CSL 104   24 V ~/ (2) 2 ... 10 V– No 1 5 150
 
CSN 238   230 V ~ (6) 2 o 3 points No 2 10 150 E 922
CSN 238/C   230 V ~ (6) 2 o 3 points 1 2 10 150
CSN 234   24 V ~/– (4) 2 o 3 points No 2 10 150
CSN 234/C   24 V ~/– (4) 2 o 3 points 1 2 10 150
CSN 204   24 V ~/– (4) 2 ... 10 V– No 2 10 150
 
CSS 438   230 V ~ (6) 2 o 3 points No 4 20 150 E 931
CSS 438/C   230 V ~ (6) 2 o 3 points 1 4 20 150
CSS 434   24 V ~/– (4) 2 o 3 points No 4 20 150
CSS 434/C   24 V ~/– (4) 2 o 3 points 1 4 20 150
CSS 404   24 V ~/– (4) 2 ... 10 V– No 4 20 150
 
CSG 838   230 V ~ (8) 2 o 3 points No 8 40 150 E 940
CSG 838/C   230 V ~ (8) 2 o 3 points 1 8 40 150
CSG 834   24 V ~/– (7) 2 o 3 points No 8 40 150
CSG 834/C   24 V ~/– (7) 2 o 3 points 1 8 40 150
CSG 804   24 V ~/– (7) 2 ... 10 V– No 8 40 150

ACCESSORIES FOR DAMPER ACTUATORS