APPLICATION
CLG ... actuator is designed for operating,with linear movement,
VL 3.. and VE 3.. 65/150 seat valves used in heating and
air-handling installations with fluid temperatures 0 ... 200 °C.
FEATURES
-
Power supply: 230 - 24 V ~.
-
3-wire electric control (Common, Opens,
Closes).
-
Protection: IP 54.
-
Max. fluid temperature valve 200 °C.
|
|
|
Valves
(up to DN) |
|
Code |
|
Power
supply V ~ (VA) |
Speed s/mm |
Run max. mm |
Force
N |
VL
... |
VF
... |
Data sheet |
CLG
328 |
|
230
(8) |
8 |
40 |
2.000 |
65 ...
100 |
65 ...
150 |
M
231 |
CLG
324 |
|
24
(8) |
8 |
40 |
2.000 |
65 ...
100 |
65 ...
150 |
CLG
168 |
|
230
(13) |
4 |
40 |
1.500 |
65 ...
100 |
65 ...
150 |
CLG
164 |
|
24
(19) |
4 |
40 |
1.500 |
65 ...
100 |
65 ...
150 |
ACCESSORIES
Code |
|
Description |
FCG
002 |
|
2
end-of-run auxiliaries 6 (2) A for
CLG ... |
ADAPTOR
Code |
|
Description |
AVL 424 |
|
Adaptor
for replacing CLC
... actuators with CLG ... |
|